Categories RCD Circuit Breaker
Brand Name: ANS
Model Number: ANS-RCBO-32A
Certification: TUV,CE
Place of Origin: China
MOQ: 1pc
Price: USD
Payment Terms: L/C, D/A, D/P, T/T, Western Union, MoneyGram
Supply Ability: 1000pcs a day
Delivery Time: 20-30days
Packaging Details: standard export package
Product name: Type B RCBO 4 poles B32 MCB
Rated Current: 32A/40A/63A
Poles: 4Pole (3P+N)
Rated breaking capacity: 6,000A
Rated frequency: 50/60Hz
Rated residual operation current: 0.03mA
Short-circuit current Inc: Ic 10000A
Standard: IEC 61008-1, IEC 62423
  • Haven't found right suppliers
  • Our buyer assistants can help you find the most suitable, 100% reliable suppliers from China.
  • And this service is free of charge.
  • we have buyer assistants who speak English, French, Spanish......and we are ready to help you anytime!
Submit Buying Request
  • Product Details
  • Company Profile

IEC 62423 32A RCD Circuit Breaker MCB RCCB RCBO With Overcurrent Protection

B Type RCCB with Overcurrent protection Type B RCBO 4 poles B32 MCB RCD Circuit Breaker


Technical Data


ModeElectronic
Type
Rated current In
B16,20,25,32,40,50,63A
Poles2P(1P+N),4P(3P+N)
2P 240V~
Rated voltage Ue
Insulation voltage Ui
4P 415V~
500V
Rated frequency50/60Hz
Rated residual operating current(I△n)30,100,300mA
Break time under I△n≤0.1s(S type <0.5s)
Rated breaking capacity6,000A
Energy limiting class3
Rated impulse withstand voltage(1.5/50) Uimp4,000V
Dielectric test voltage at ind.Freq. for 1min2kV
Pollution degree2
Thermo-magnetic release characteristicB,C

Application

  • The function of lightning and surge protectionsystemsistoprotect the devices,functionalisolations and overvoltage-sensitive consumerequipments ofenergy distributionsystemsagainstall lightning and overvoltage
  • damages.whole building;the outdoor lightningprotection system is generally notsufficienttoeliminate suchmalfunctions.At most of types,thedefected protection devicecan be made
  • operative again by changing the damaged insert;these variants are also equipped with bothopticaloperation signaland auxiliary statuscontact.

Mechanical Features


Electrical life4,000 Cycles
Mechanical life
Contact position indicator
10,000 Cycles
Yes
Protection degreeIP20
Reference temperature for setting of thermal element30℃
Ambient temperature (with daily average≤35℃)-5℃~+40℃
Storage temperature-25℃~+70℃


Installation


Terminal connection type
Terminal size top/bottom for cable
Cable/Pin-type busbar/U-type busbar
25mm2 18-3AWG
Terminal size top/bottom for busbar25mm2 18-3AWG
Tightening torque2.5Nm 22In-lbs
MountingOn DIN rail EN60715(35mm) by means of fast clip device
ConnectionFrom top

Combination with accessories
Auxiliary contactEKM1-OF
Alarm contact
Shunt release
EKM1-FB
EKM1-MX

Tripping Current Range
Lagging Angle
I△n>0.01A
0.35I△n≤I△≤1.4I△n
I△n≤0.01A
0.35I△n≤I△≤2I△n
90°0.25I△n≤I△≤1.4I△n0.25I△n≤I△≤2I△n
135°0.11I△n≤I△≤1.4I△n0.11I△n≤I△≤2I△n



Certification:TUV