Sign In | Join Free | My disqueenfrance.com
disqueenfrance.com
Products
Search by Category
Wholesale Marketplace
Home > Level Measuring Instruments >

Single Phase Energy Meter Calibration Equipment For Single Energy Meter Automatic Test Line In Mass Production

Categories Energy Meter Automatic Test Pipeline
Brand Name: GENY
Model Number: YCATS I / YCATS II
Certification: ISO, CE
Place of Origin: China
MOQ: 1
Price: negotiate rates
Payment Terms: T/T, L/C, D/P, T/T
Supply Ability: 2 sets/ 3 months
Delivery Time: 6~8weeks
Packaging Details: Plywood cases
Communication Protocol: Modbus RTU, Modbus TCP, DNP3.0
Control Software: Graphical user interface (GUI)
Dimensions: Customizable based on customer's requirements
Test Frequency: 50Hz/60Hz
Accuracy Level: 0.05%, 0.1%, 0.2%
Testing Standards: IEC 62053-21, IEC 62053-22, IEC 62053-23
Power Supply: 220V/110V, 50Hz/60Hz
Application: Energy meter testing
Operating System: Windows
Test Voltage Range: 0-500V
Test Current Range: 0-200A
Function: Automatically test energy meters for accuracy and functionality
  • Haven't found right suppliers
  • Our buyer assistants can help you find the most suitable, 100% reliable suppliers from China.
  • And this service is free of charge.
  • we have buyer assistants who speak English, French, Spanish......and we are ready to help you anytime!
Submit Buying Request
  • Product Details
  • Company Profile

Single Phase Energy Meter Calibration Equipment For Single Energy Meter Automatic Test Line In Mass Production

Single Phase Energy Meter Calibration Equipment for Single Energy Meter Automatic Test Line in Mass Production

Description:

The Single Energy Meter Automatic Test Line is specially designed for automatic test of single – phase energy meters in mass production.

Applications:

· Electric power departments

· Electric energy meter manufacturers

· Measuring and quality examining departments

Features:

1) Accuracy: 0.1% , 0.05%

2) The breakdown of power source of MUT only affects one meter position unit, and the other positions still work normally, so the system is more reliable.

3) Each meter position unit with a power source and connect in parallel. The unit is totally separated, don't affect each other, eliminating the effect of large power output in stability of power source reducing error, and improving test accuracy.

4) The meter with different testing ranges, constants protocols can be tested together because each meter position unit are in parallel, which does not affect each other.

5) More meter position, less installation waiting time. Effective test time is shorter, only 30% of conventional test Methods.

6) Test single phase meter with closed link. Expansion of meter position units is easy and convenient.

7) Automatic meter loading /unloading and test, with PC control by Ethernet communication.

8) Flow of work: meter loading, indentation, location, testing, defect sorting, labeling, lead sealing, packaging, Return to meter's warehouse.

Functions:

· Error test

· Starting and creeping test

· Time base test

· Time consumption switch test

· Demand test

· Withstand voltage test

· Influence test

· Dial test


Application Conditions and Requirements

EnvironmentPower RequirementSafety
Operation
Temperature
HumidityAltitudeVoltage SupplyIP ClassConformity
-10°C--+40ºC35%--85%<2500m3x220/380V±10%
(or customized)
50/60Hz±2Hz
IP30CE conform

TypeYCS-103-250YCS-103-800YCS-103-1200YCS-203-2500
Voltage
Test voltage output(Phase-Neutral)3x(24V-300V)(or customized)
Power of the voltage outputMax.3x100VAMax.3x250VAMax.3x500VAMax.3x1000VA
ResolutionBetter than 0.01%of full scale value of range
Setting accuracyBetter than 0.05% at the final range value
StabilityBetter than 0.005%/h(integration time 150 s)
Load regulation from 0-max.loadBetter than 0.01%
Distortion factorBetter than 0.3% for linear resistance load
Harmonics2nd-41st free programmable
Current
Test current output3x(1mA-120A/200A)
Power of the current outputMax.3x250VAMax.3x500VAMax.3x1000VAMax.3x2000VA
ResolutionBetter than 0.01% of full scale value of range
Setting accuracyBetter than 0.05%at the final range value
StabilityBetter than 0.005%/h(integration time 150 s)
Load regulation from 0-max.loadBetter than 0.01%
Distortion factorBetter than 0.3% for linear resistance load
Harmonics2nd-41st free programmable
Phase angle
Range0-360°
Resolution0.01°
Setting accuracy0.1°
Frequency
Range45Hz-65Hz
Resolution0.01Hz
Error display
Type of error displayRed LED
Resolution of the error displays8 digits



Quality Single Phase Energy Meter Calibration Equipment For Single Energy Meter Automatic Test Line In Mass Production for sale
Send your message to this supplier
 
*From:
*To: Guangzhou GENY Electric Co., Ltd
*Subject:
*Message:
Characters Remaining: (0/3000)
 
Inquiry Cart 0